750V 60°C PVC INSULATED AND SHEATHED FLEXIBLE CABLE.

NUMBER OF CORES : Up to 4 cores.
CONDUCTOR : Flexible annealed copper wires.
Sizes 0.5 mm2 up to 95 mm2for single core.
0.5 mm2 up to 35 mm2 for multi core.
INSULATION : PVC
Colour: Single core
2 core
3 core
4 core
– Black
– Light grey, Black
– Light grey, Black, Red.
– Light grey, Black, Red, Blue.
SHEATH : PVC.
:Colour: Black
CLASSIFICATION : Maximum conductor temperature 60°C
CIRCUIT G VOLTAGE : Circuit voltage not exceeding 750 volts.

600/1000 Volts
Flexible anealed Copper wires
0.5 mm2 up to 95 mm2 for Single core
0.5 mm2 up to 35 mm2 for Multi Core.
Circuit Voltage not exceeding 750 Volts

250V 60°C PVC INSULATED AND SHEATHED FLAT TYPE, FLEXIBLE CONDUCTOR.

NUMBER OF CORES : 2 cores.
CONDUCTOR : Flexible annealed copper wires, size 0.5 mm2 up to 35 mm2 PVC
INSULATION : PVC
Colour: Lightgrey,black PVC
SHEATH : PVC.
:Colour: BlackBlack or white
CLASSIFICATION : Maximum conductor temperature 60°C
: Circuit voltage not exceeding 250 volts.

250V 60°C PVC INSULATED AND SHEATHED FLAT TYPE, FLEXIBLE CONDUCTOR.

NUMBER OF CORES : 2
CONDUCTOR : Flexible annealed copper wires, size 0.5 mm2 up to 2.5 mm2
INSULATION : PVC
Colour: Any colour with one different colour tracer on lateral  side of wire, or colour thread at one of conductors
CLASSIFICATION : Maximum conductor temperature 60°C
CIRCUIT VOLTAGE : Circuit voltage not exceeding 250 volts.

250V 60°C PVC INSULATED FLEXIBLE CONDUCTOR, SINGLE CORE.

CONDUCTOR : Flexible annealed copper wires, size 0.5 mm2 up to 2.5 mm2
INSULATION : PVC – Any colour.
CLASSIFICATION : Maximum conductor temperature 60°C
CIRCUIT VOLTAGE : Circuit voltage not exceeding 250 volts.

CURRENT RATINGS
FLEXIBLE CORDS PVC TO BS 6500

PVC insulated (non-armoured) cables

The above ratings apply where coarse excess current protection is provided and are subject to voltage drop consideration
+ These ratings are for flat cables 1 mm2 to 16mm2 inclusive and circular cables 25mm2 and 35mm2
For ratings of circular cables 1 mm2 to 16mm2 inclusive refer to I.EE Regulations.

VOLTAGE GRADES

PVC or insulated (non-armoured) cables
Approximate voltage drop per ampere per metre

+ Voltage drops are for flat cables 1 mm2 to 16mm2 inclusive and circular cables 25mm2 and 35mm2
For volt drop ratings of circular cables 1 mm2 to 16mm2 inclusive refer to I.E.E. Regulations.

VOLTAGE DROP

Cable described as 600/1000 volt are suitable for use on a circuit where the voltage to earth does not exceed 600 volt and between conductors, 1000 volt. Cables, flexible Cables and Flexible Cords described as 450/750 volt. Cables. Flexible Cables and Flexible Cord described as 300/500 volt are suitable for use on a circuit where the voltage to earth does not exceed 300 volt and between conductors, 500 volt, Total volt drop between consumers terminals and any other part of the installation must not exceed 2.5% of the nominal voltage. Refer lEE Regulation & ERA Report.